Retrofitting Strategy Re-allocation of office layout plan and/or lighting distribution plan to maximise daylight penetration and match the demand
Office can be renovated to maximise the utilisation of natural day light.

Consideration
  • Barriers to natural lights such as high cabinets, and partitions should be reduced.
  • Light-coloured furniture and wall painting should be used.
  • Light shelf can be installed if suitable, to reflect external light to the ceiling of inner zones of the space.
  • Daylight sensors can be used to dim down the perimeter zone lighting level when natural light is adequate. Care is to be taken as to contradicting the operation of the curtain for preventing glare when the curtain comes down and the artificial lights are at max lux level. 
Estimated Saving

kW_LGTPRE*NLGTPRE*LFPRE*OPHRPRE,yr – kW_LGTPOST*NLGTPOST *LFPOST*OPHRPOST,yr

Where  LFPRE = 1 for ON/OFF control under normal operating time of premises

LFPOST =LF1*IFA1,POST/IFA + LF2*IFA2,POST/IFA + … + LFi*IFAi,POST/IFA

LFi = (1 – 0.33*0.5) = 0.85 for 33% power reduction (dim-down to 50% lux level) at 50% of time as an example

IFA = internal floor area

IFAi,POST = effective IFA where improvement taken place

OPHR,yr = hr/day*day/wk*52