Retrofitting Strategy Zoning the carpark for operation mode
Divide the carpark into zones and close down some zones during night time or non-peak hours so that lighting and ventilation needs can be reduced.

Consideration
  • Security risks need to be addressed and planned for. 
  • May need to rearrange the zoning for monthly or sold carparks to maximise the benefit of the retrofit.
Estimated Saving

IFA1/IFACP*(kW_MVF1*NMVF1*LFPRE*OPHRPRE,yr – kW_MVF1*NMVF1*LFPOST*OPHRPOST,yr) +

IFA2/IFACP*(kW_MVF2*NMVF2*LFPRE*OPHRPRE,yr – kW_MVF2*NMVF2*LFPOST*OPHRPOST,yr) +…

IFAi/IFACP*(kW_MVFi*NMVFi*LFPRE*OPHRPRE,yr – kW_MVFi*NMVFi*LFPOST*OPHRPOST,yr)