[0.605*(LFSM,PRE – LFSM,POST) + 0.395*(LFWN,PRE – LFWN,POST)]*NAHUPRE*kW_AHUPRE * OPHR,yr
Where LFAHU,POST = LFAHU,PRE * [(DP_FLTPRE – P_FLTPOST) / DP_AHUF]
For VSD: LFSM = 0.795, LFWN = 0.562;
For EC or DC-motor: LFSM = 0.71, LFWN = 0.38
OPHR,yr = hr/day*day/wk*52
Please click HERE to view the list of terminology.
|